Update CM2013 13.0.0.06 Readme



 
 

Contents

I. Deliverable
II. Requirement
III. Installation Instructions
IV. List of fixes in this Update



I. Deliverable

This update is delivered in a multi-languages EXE file with an html readme file.
It can be identified in the user interface of the setup by a SetupID value equal to 0306.

II. Requirement

ControlMaestro 2013 must be installed.

III. Installation Instructions

1) Close any running instance of the application

2) Launch the installer by double clicking on Update_CM_13_0_0_06.exe and follow the instructions

3) Restart your application

Silent installation:
A silent installation without displaying wizard or the background can be performed using the option on the command line. This silent mode only displays the installation progress window.

Command line usage: Update_CM_13_0_0_06.exe /SILENT


IV. List of fixes in this Update

ECR 6562: Giessen: Load Event Viewer failed

ECR 6531: Codesys still in demo mode when unplug and plug the dongle

ECR 6529: Edit trigger definition not available after an dynamic definition on an object

ECR 6523: Alarms are not in right order in Event Summary

ECR 6520: Date format in CSV export for charts

ECR 6518: List Viewer: No error messae on the 'home page' if event viewer check throws error

ECR 6510: Comment containing the character @ in CM Langage

ECR 6503: UTF8 characters are not supported in line printing mode

ECR 6500: AAM Backup user not correctly saved

ECR 6486: EBM Münchstein : Crash

ECR 6477: in JavaFastAction; please wait dialogbox is not automaticaly closed

ECR 6469: Bacnet station backup works only one time

ECR 6458: Not possible to edit a cluster in the cluster-edit-tool

ECR 6424: Bacnet driver : ahp file name cut after 11 characters in the bacnet.log file

ECR 6419: Image with a trigger defined on a cluster which contains already a trigger action in its instance cannot be opened in web

ECR 6401: Web pages with tag context are loaded very slowly from a remote client

ECR 6370: Bacnet Object View : wrong unit in the general tab

ECR 6349: $ASK query doesn't work in a cluster with fast action trigger (set tagvalue)

ECR 6101: If the plug is missing in a running application the CMSoftPLC Runtime stops after 2h; other modules (CM; AAM; Scheduler) will run for 24h

ECR 5689: When deleting a Tag that was used in CMLanguage then the statement of that Tag disappears

V. List of fixes from previous updates

ECR 6516: Databox text color option

ECR 6505: Write backup history failed when there is a VfiBackup file

ECR 6504: SecurityException when using Java 7.51

ECR 6499: Java is blocked when opening an alarm comment created with a previous version and containing special characters

ECR 6497: CM crash at import of a GIF animation

ECR 6495: Application freeze when switching users

ECR 6490: GIF Animation slows down and freezes

ECR 6480: on web; direct trigger misses to show decimals digits from converted integer

ECR 6479: values under 1 on Y axis logarithmic not managed

ECR 6475: Dialog boxes for tags have an issue with fonts

ECR 6474: CM freezes in an application with many MultiState

ECR 6473: time direct trigger on web doesn't work

ECR 6472: Leak of memory when opening/closing chart

ECR 6468: history ODBC bcakup files re-injection process; after connection loss; is too long

ECR 6467: ControlMaestro crash after a fem replacement of the alarms

ECR 6461: Sometimes sound appears without Popup or popup appears without sound

ECR 6460: List Viewer : deleted tags are still present in the tag filter list

ECR 6452: EXIST language command with string tag value dynamic file extension can't work

ECR 6449: Crash : after opening a chart with a tag which was deleted

ECR 6442: alarm history files can't be read after history folder connection loss

ECR 6435: Alarm Filter : When we removed the "all stations" properties in the network tab and put a single station; the character "P" is written is all fields from others filters

ECR 6434: MRP backup PLC does not work (write is not possible)

ECR 6433: List Viewer : On a multi-server installation; tags coming from a remote application are always shown offline even if values are correclty sampled and displayed

ECR 6427: Alarmtext no longer displays floating point values for tags with (un)signed format

ECR 6424: Bacnet driver : ahp file name cut after 11 characters in the bacnet.log file

ECR 6422: SQL VFIalarm fifi stack management

ECR 6421: Web : Tags which are in communication error cannot be locked

ECR 6419: Image with a trigger defined on a cluster which contains already a trigger action in its instance cannot be opened in web

ECR 6416: Stationname Tooltip is wrong displayed

ECR 6414: List Viewer: When a user changes tabs before the data has finished loading - the outstanding requests can block further requests

ECR 6411: SQL VFITag fifo stack management

ECR 6403: Cluster: $ASK with suffix in alarm family does not work when we put the station name before instantation

ECR 6402: CMServiceHost crashes on starting CM

ECR 6398: VFISQL : When we stop loading data in history viewer; this one can not load anything anymore

ECR 6396: VFISQL : When SQL database is splitted; it is no more possible to read the old historical files

ECR 6394: History Viewer in web : wrong translation in the configuration menu

ECR 6393: Using fast action loadimage Goto previous zone (<<<) problem

ECR 6391: Progress bar for deleting Tags

ECR 6388: No request from CM after huge Tag import(over65535)

ECR 6385: Unacked alarm number is not the same in Web and in Studio Event Summaries

ECR 6384: Event Viewer : Action "Go to zone" for an alarm does not work with a remote web client

ECR 6383: Some fast action description not translated

ECR 6376: Trigger on cluster is deleted when the cluster is rebuild

ECR 6374: VFISQL : sql user cannot be defined with a password with at least 5 capital letters

ECR 6373: List Viewer : Logout function does not work - Web client restart need to be done

ECR 6369: List Viewer : Bacnet Devices and Proprietary objects are always shown offline even if they are online

ECR 6368: List Viewer : Decimal Point number is not respected with multi state tags

ECR 6365: bacnet object windows don't work in webdesktop.

ECR 6360: Invalid license message appears on errors.dat and event viewer with master/backup architecture

ECR 6358: when network remote history folder is not accessible; CM can't start.

ECR 6357: Menue-Authorisation in web does not work as expected with regional-settings in russian

ECR 6354: Chart is always displayed in a little window when we open it despite we save it with maximize size

ECR 6353: SQL Alarm : Old alarms imported with the import tool are not displayed in the event summary

ECR 6352: German translation : Alarm condition contextual menu is in english

ECR 6350: German translation : Replace "Verbindung erforderlich" by "Anmeldung erforderlich" in Alarm definition

ECR 6349: $ASK query doesn't work in a cluster with fast action trigger (set tagvalue)

ECR 6347: LKH Blutbank : Crash when sending an AAM alarm and centralized user management is activated

ECR 6337: Impossible to type some characters in edit box of Alarm Family in Image dialog box alarm definition

ECR 6330: crash when changing the URL from the webscheduler

ECR 6321: WebScheduler issues in Internet Explorer 10

ECR 6317: German Umlaut (i.e. Ü) in image name causes layouts in web to fail opening images with "configuration file not found"

ECR 6314: fter a while List Viewer is blocked we have the error "Load failed"

ECR 6313: When opening an event summary from an image; memory of ControlMaestro.exe increase quickly and lead to a crash of the process

ECR 6310: Webscheduler is not compatible with IE10

ECR 6308: CrashCMServiceHost if user is not admin

ECR 6307: importing tag in csv format is not working with XP SP3

ECR 6303: EluCoreSVC : After windows restart, the "EluCore" service does not start automatically (EluDB is present on a local SQL database)

ECR 6301: German translation : Replace "Wichtung" by "Zone" in zone and trigger definition

ECR 6299: System Security doesn't work correctly in ControlMaestro 2011 PP 28

ECR 6291: Charts in step + filled cannot be hidden

ECR 6290: Characters badly displayed when print in listing mode of alarms

ECR 6288: Impossible to print a web event summary in historical mode - For EventSummary, distinguish Normal/Template mode from Online/Offline. - Toolbar, menu and printing are only displayed/allowed in normal mode. for HTML Template

ECR 6287: Different displaying animations between studio and web when we have an error communication

ECR 6281: Audit Trail : don't Trace AutoAck from Alarms; no action is done by a User [IN:010450]

ECR 6279: the @ between quotes can't be used in language.

ECR 6278: image copy/paste of trigger object that contains action formula to fill a string content truncates copied formula to 11 characters

ECR 6277: Charts : crash or freeze with network tag disconnected

ECR 6269: column from web event summary are unreadable.

ECR 6236: NTP synchronisation create connection loss with charts

ECR 6229: Chart problems when displaying historical data which contain communication error

ECR 6166: The function "User Comment" does not work for alarms in a Master/Backup installation.

ECR 6155: Arnika Apotheke : Crash

ECR 6098: Crash

ECR 6063: modify property of dynamic object do not test tag validity. - display a messagebox with tag name when the given tag is invalid

ECR 6034: Its not possible to use a multistate StateText in the CM language or eventsummery

ECR 5980: CMSql writes german umlaut wrong in the datasource

ECR 5783: Event summaries with multiple filters

ECR 5729: Ctrl+Alt+Suppr is not disable whereas the system security is Full

ECR 5683: Error message 'Cannot add a new element, the container is full' appears sometimes when opening chart

ECR 5500: Crash while using netsim.dat

ECR 4649: multiple-add tag: number of steps limited

ELUTIONS
European Headquarter

Parc Technologique de Lyon
12 allée Irène Joliot-Curie
(Bâtiment B1)
F-69791 Saint-Priest Cedex
tel:   +33 (0)4 72 47 98 98
fax:  +33 (0)4 72 47 98 99

info@elutions.com
www.elutions.com | www.getcontrolmaestro.com

Standard Support
Web: http://support.elutions-europe.com
Email: support@elutions-europe.com
Fax:  +33 (0)4 72 47 98 99


 
©2014 ELUTIONS. All rights reserved, ControlMaestro, Wizcon, Wizcon Supervisor, Maestro, ControlMaestro, KernelPro, Web Scheduler, Notifier, NotifierVoice, OPC Suite, BACnet Suite, Database Logger, Replay, Excel Reporter, Web Activity Summary, CAD Converter, Tag Template, Alarm Template, DB Generator, WAGO Importer, Directory Manager, and ControlMaestro PID are trademarks or registered trademarks of ELUTIONS. ControlMaestro Premium Maintenance and ControlMaestro Hotline Plus are service marks of ELUTIONS. BACnet is a registered trademark of ASHRAE. All other trademarks are property either of ELUTIONS or of their respective owners.